Bryant 593C User Manual page 5

Electric air conditioner
Table of Contents

Advertisement

UNIT SIZE
Operating Weight (Lb)
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range*
Compressor— Rated Load Amps
Locked Rotor Amps
Condenser Fan Motor—Full Load Amps
Min Unit Ampacity for Wire Sizing
Min Wire Size (75°C Copper) AWG†
Min Wire Size (60°C Copper) AWG†
Max Wire Length (Ft) (75°C Copper)‡
Max Wire Length (Ft) (60°C Copper)‡
Max Branch Circuit Fuse Size**
COMPRESSOR and REFRIGERANT
Compressor—Manufacturer and Type
Temperature and Current Protection
Refrigerant—Type and Amount (Lb)††
CONDENSER COIL and FAN
Coil Face (Sq Ft)
Fins per In.—Rows—Circuits
Fan Motor—HP, Type, and RPM
Volts—Hertz—Phase
Condenser Airflow (CFM)
OPTIONAL EQUIPMENT
Support Feet
Coastal Filter
Time Delay Relay
Cycle Protector
Crankcase Heater
Start Assist—Capacitor/Relay Type
Start Assist—PTC Type
Sound Hood
TXV Kit (RPB)
TXV Kits (Hard Shutoff)
Low-Pressure Switch
High-Pressure Switch
Filter Drier
Evaporator Freeze Thermostat**
Liquid-Line Solenoid Valve
Winter Start Control**
Low-Ambient Kit
MotorMaster® Control††
Ball Bearing Fan Motor
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Builder's Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
Outdoor Air Temperature Sensor
Backplate for Non-Programmable
Thermostat
Backplate for Programmable Thermostat
Backplate for Builder's Thermostat
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors per the NEC (ANSI/NFPA 70) Article
336-26. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required. See Low-ambient controller Installation Instructions for application.
NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
SPECIFICATIONS Continued
042-C, D
206
19.0
105.0
1.4
25.2
10
10
73
77
40
Copeland Reciprocating
Internal Line Break
R-22 and 5.51
12.2
20—1—2
Standard
KSAHS1301AAA
KSASH1201COP
KAATX0501RPB
KSATX0601HSO
—5—
048-C
199
208–230—60—1
197—253
24.4
140.0
1.4
31.9
10
8
59
97
50
Millennium Scroll
Internal Line Break and Dome Thermostat
R-22 and 7.63
15.2
25—1—3
1/4 PSC and 1100
208/230—60—1
3000
KSASF0101AAA
KAACF0801MED
KAATD0101TDR
KSACY0101AAA
KAACH1201AAA
KSAHS1601AAA
KAACS0201PTC
KSASH2001CYL
KAATX0601RPB
KSATX0701HSO
KAALP0101LPS
KSAHI0101HPS
P502-8163S (RCD)
KAAFT0101AAA
KAALS0101LLS
KAAWS0101AAA
KSALA0201R22
32LT660004 (RCD)
HC40GE232 (RCD)
TSTATBBNAC01-B
TSTATBBPAC01-B
TSTATBBBAC01-B
TSTATBBPRH01-B
TSTATBBSEN01-B
TSTATXXNBP01
TSTATXXPBP01
TSTATXXBBP01
TSTATXXCNV10
060-C
217
28.8
165.0
1.4
37.4
8
8
78
82
60
Millennium Scroll
R-22 and 10.63
18.3
25—1—4
KAATX0701RPB