ELECTRIC
AIR CONDITIONER
Model 593C Energy-Efficient Air Conditioners incor-
porate innovative technology to provide quiet, reliable
cooling performance. Built into these units are the fea-
tures most desired by homeowners today. Standard
SEER ratings of 10.0 can reach as high as 11.2 when
combined with specific Bryant equipment. All models
are listed with ARI, UL (U.S. and Canada), and CEC.
AVAILABLE OPTIONS
ELECTRICAL RANGE —All units are offered in 208–
230v single phase.
WIDE RANGE OF SIZES —Available in 7 nominal
sizes from 018 through 060 to meet the needs of resi-
dential and light commercial applications.
Model 593C (60 Hz)
WEATHER-PROTECTIVE CABINET —Steel is galvanized and
coated with a layer of zinc phosphate. A coat of modified poly-
ester powder coating is then applied and baked-on, providing
each unit with a hard, smooth finish that will last for many years.
All screws on cabinet exterior are ceramic coated for a long-
lasting, rust-resistant, quality appearance.
HEAVY DUTY INLET GRILLE —The DuraGuard™ coil protec-
tor, made of a coated steel wire grid with vertical 3/8 in. spacing,
is designed to help protect the coil from inclement weather, van-
dalism, and incidental damage. It provides protection while not
restricting airflow and maintaining ease of coil inspection and
cleaning.
TOTALLY ENCLOSED FAN MOTOR —Means greater reliability
under adverse weather conditions and dependable perfor-
mance for many years. The permanent-split-capacitor type
motor was designed for optimum efficiency. Then the motor was
tested and qualified under extreme conditions to help ensure
the greatest reliability.
UNIT DESIGN —Copper tube, enhanced aluminum fin coil is
designed for optimum heat transfer. Vertical air discharge car-
ries sound and hot condenser air up and away from adjacent
patio areas and foliage. Heat pump-style drain pan for easy
removal of water, dirt, and leaves.
BRYANT'S AEROQUIET SYSTEM —Extremely low operating
sound is the result of special attention to the air moving through
the outdoor unit, and a specially designed sound enclosure sur-
rounding the compressor to eliminate sound transmission to the
rest of the systems.
APPLICATION VERSATILITY —The 593C can be combined
with a wide variety of evaporator coils and blower packages to
provide quiet, dependable comfort. Unit can be installed on a
roof or at ground level on a slab.
EXTERNAL SERVICE VALVES —Both service valves are
brass, front seating type with sweat connections. Valves are
externally located so refrigerant tube connections can be made
quickly and easily. Each valve has a service port for ease of
checking operating refrigerant pressures.
EASY SERVICEABILITY —One access panel provides access
to electrical controls and compressor. Removal of wire dome
gives access to fan motor and removal of the top gives access
to the coil. For improved serviceability, all models are equipped
with a compressor terminal plug.
COMPRESSOR PROTECTION —Each model is protected with
internal temperature- and current-sensitive overloads. An inter-
nal pressure relief valve provides high-pressure protection to
the refrigerant system.
LIMITED WARRANTY —Standard 5-year warranty on all parts,
with an additional 10-year warranty on compressor.
Form No. PDS 593C.18.7
Sizes 018 thru 060

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 593C

  • Page 1: Electric Air Conditioner

    APPLICATION VERSATILITY —The 593C can be combined with a wide variety of evaporator coils and blower packages to provide quiet, dependable comfort. Unit can be installed on a roof or at ground level on a slab.
  • Page 2 —2—...
  • Page 3 LIQUID TUBE DIAMETER (IN.) UNIT 0 to 50 Ft SIZE Tube Length 018, 024 030, 036 042, 048 * For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. * Piston listed is for any approved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil.
  • Page 4: Specifications

    UNIT SIZE Operating Weight (Lb) ELECTRICAL Unit Volts—Hertz—Phase Operating Voltage Range* Compressor— Rated Load Amps Locked Rotor Amps Condenser Fan Motor—Full Load Amps Min Unit Ampacity for Wire Sizing Min Wire Size (75°C Copper) AWG† Min Wire Size (60°C Copper) AWG† Max Wire Length (Ft) (75°C Copper)‡...
  • Page 5 UNIT SIZE Operating Weight (Lb) ELECTRICAL Unit Volts—Hertz—Phase Operating Voltage Range* Compressor— Rated Load Amps Locked Rotor Amps Condenser Fan Motor—Full Load Amps Min Unit Ampacity for Wire Sizing Min Wire Size (75°C Copper) AWG† Min Wire Size (60°C Copper) AWG† Max Wire Length (Ft) (75°C Copper)‡...
  • Page 6 An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE: All units where Low-Ambient Controller has been added. 8. Filter Drier A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow. SUGGESTED USE: All split-system air conditioners. 9. High-Pressure Switch Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit.
  • Page 7 ACCESSORY DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Relay An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. 18.
  • Page 8 COILS + 355MAV042080 VARIABLE-SPEED FURNACE 22,600 NONE 11.00 22,600 NONE 11.00 23,200 NONE 11.20 22,600 NONE 11.00 23,200 NONE 11.20 —8— BRYANT GAS FURNACE OR ACCESSORY ACCESSORY TDR† TXV‡ 10.50 10.50 11.00 11.00 11.00 11.00 11.00 11.00 11.00 11.00 11.00 11.00...
  • Page 9: Combination Ratings Continued

    NONE 29,000 NONE 29,000 NONE 29,000 NONE 29,000 NONE COILS + 355MAV060120 VARIABLE-SPEED FURNACE 29,000 NONE 29,000 NONE 29,000 NONE —9— BRYANT GAS FURNACE OR STANDARD ACCESSORY ACCESSORY RATING TDR† TXV‡ 10.00 10.20 10.20 10.10 10.50 10.50 10.00 10.20 10.20 10.10...
  • Page 10 33,000 32,600 33,000 33,000 33,000 33,000 COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE 33,000 33,000 33,000 32,600 33,000 33,000 33,000 33,000 33,000 —10— BRYANT GAS FURNACE OR STANDARD ACCESSORY ACCESSORY RATING TDR† TXV‡ 10.00 10.20 10.20 10.00 10.20 10.20 10.00 10.20 10.20 10.00...
  • Page 11 40,000 39,500 40,000 39,500 39,500 40,000 COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE 39,500 39,000 39,500 40,000 40,000 39,500 40,000 39,500 40,000 —11— BRYANT GAS FURNACE OR STANDARD ACCESSORY ACCESSORY RATING TDR† TXV‡ 11.00 — 11.00 10.50 — 10.50 10.50 — 10.50 10.50...
  • Page 12 46,000 NONE 46,000 NONE 44,500 NONE 46,000 NONE 46,000 NONE 47,500 NONE 46,000 NONE 46,000 NONE 46,500 48,000 —12— BRYANT GAS FURNACE OR STANDARD ACCESSORY ACCESSORY RATING TDR† TXV‡ 10.15 10.25 10.15 10.25 10.25 10.15 10.15 10.05 10.25 10.3 10.2 10.2...
  • Page 13 NONE 45,500 NONE 47,000 NONE COILS + 355MAV060120 VARIABLE-SPEED FURNACE 45,000 NONE 45,500 NONE 45,500 NONE 45,000 NONE 47,000 NONE —13— BRYANT GAS FURNACE OR STANDARD ACCESSORY ACCESSORY RATING TDR† TXV‡ 11.00 — 11.00 10.40 — — 10.50 — —...
  • Page 14 † In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Bryant furnaces are equipped with TDR.
  • Page 15 EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C018-C, D Outdoor Section With CC5A/CD5AA018 Indoor Section 19.7 9.50 1.69 17.9 11.8 1.65 16.1 14.0 1.60 15.0 15.0 1.58 20.1 9.89 1.73 18.3 12.5 1.68 16.5 14.9 1.64 15.7 15.7 1.62 20.5 10.3 1.76...
  • Page 16 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C024-C, D Outdoor Section With CC5A/CD5AA024 Indoor Section 26.3 12.9 2.34 24.0 16.2 2.27 21.7 19.3 2.20 20.5 20.5 2.17 26.8 13.4 2.40 24.5 17.1 2.33 22.2 20.6 2.26 21.4 21.4...
  • Page 17 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C030-C, D Outdoor Section With CC5A/CD5AA030 Indoor Section 32.6 15.9 2.90 29.7 20.0 2.83 26.9 23.9 2.74 25.4 25.4 2.69 33.2 16.6 2.97 30.4 21.2 2.89 1000 27.5 25.4 2.81 26.5...
  • Page 18 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C036-C, D Outdoor Section With CC5A/CD5AA036 Indoor Section 39.6 19.6 3.42 36.0 24.9 3.32 1050 32.7 29.8 3.23 31.3 31.3 3.19 40.3 20.5 3.49 36.7 26.4 3.40 1200 33.4 31.8 3.31...
  • Page 19 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C036-C, D Outdoor Section With CC5A/CD5AA036 Indoor Section Continued 39.6 19.6 3.42 36.0 24.9 3.32 1050 32.7 29.8 3.23 31.3 31.3 3.19 40.3 20.5 3.49 36.7 26.4 3.40 1200 33.4 31.8...
  • Page 20 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C042-C, D Outdoor Section With CC5A/CD5AA042 Indoor Section 45.2 22.4 4.01 41.2 28.3 3.89 1225 37.4 34.0 3.77 35.9 35.9 3.72 46.0 23.4 4.10 42.0 30.1 3.98 1400 38.2 36.2 3.86...
  • Page 21 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C042-C, D Outdoor Section With CC5A/CD5AA042 Indoor Section continued 45.2 22.4 4.01 41.2 28.3 3.89 1225 37.4 34.0 3.77 35.9 35.9 3.72 46.0 23.4 4.10 42.0 30.1 3.98 1400 38.2 36.2...
  • Page 22 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C048-C Outdoor Section With CC5A/CD5AA048 Indoor Section 54.9 27.0 4.53 50.1 34.1 4.42 1450 45.6 41.0 4.33 43.5 43.5 4.29 55.6 27.9 4.61 50.8 35.6 4.50 1600 46.3 42.9 4.40 44.7...
  • Page 23 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C048-C Outdoor Section With CC5A/CD5AA048 Indoor Section continued 54.9 27.0 4.53 50.1 34.1 4.42 1450 45.6 41.0 4.33 43.5 43.5 4.29 55.6 27.9 4.61 50.8 35.6 4.50 1600 46.3 42.9 4.40...
  • Page 24 DETAILED COOLING CAPACITIES* Continued EVAPORATOR Capacity Total MBtuh† System Total Sens‡ kW** 593C060-C Outdoor Section With CC5A/CD5AW060 Indoor Section 66.9 33.0 5.85 61.1 41.8 5.70 1750 55.7 50.3 5.56 53.2 53.2 5.50 68.1 34.5 5.98 62.3 44.2 5.82 2000 56.8 53.4 5.69 55.2...
  • Page 25 °F 17.9 75.7 1.10 19.8 77.7 1.13 21.8 79.9 1.15 24.0 82.3 1.18 26.3 84.9 1.20 28.6 87.6 1.23 24.0 81.3 1.52 26.6 83.6 1.57 29.4 86.2 1.61 32.3 88.9 1.66 35.3 92.0 1.71 38.4 95.3 1.76 30.2 81.3 1.88 33.5 83.4 1.93...
  • Page 26 °F 40.6 81.5 2.56 44.8 83.7 2.63 49.3 86.1 2.69 54.0 88.7 2.76 58.9 91.4 2.82 64.1 94.3 2.89 44.5 80.0 2.76 48.7 81.8 2.81 53.1 83.7 2.86 57.8 85.8 2.92 62.7 88.0 2.99 67.9 90.4 3.06 55.9 84.5 3.47 61.1 86.7 3.54...
  • Page 27 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without low ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4.
  • Page 28: Guide Specifications

    Condenser fan will be direct-drive propeller type, discharging air upward. © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Table of Contents