B.4: Controlling Nacs, Aux Power, And Door Holders With Nac Sync - Honeywell Fire-Lite FL-PS6 Instruction Manual

Table of Contents

Advertisement

Application Examples
B.4 Controlling NACs, Aux Power, and Door Holders with NAC Sync
In this application, use of a single CDRM-300 mounted inside the cabinet can monitor the two power supply trouble relays and trigger
two independent inputs via relay circuits. FL-PS outputs #1 and #2 are being used for 24 VDC aux power triggered by the module's relay
circuits. Any FL-PS output circuit can be configured to follow any input circuit.
End-of-Line Resistors
supplied with Module
TB4
TB15
Figure B.4 Controlling NACs, Aux Power, and Door Holders with One Input and NAC Sync
The following notes apply to Figure B.4.
Any output circuit can be configured as NAC, door holder, or 24VDC power.
Refer to Section 3 for instructions on setting the DIP switches.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed between terminals 1 and 4 for module wiring supervision (the ELR value is dependent
on the module/FACP employed).
An End-of-line Resistor on input circuits#1-2 (TB5-6) are optional for this particular application.
Ensure that the CDRM-300 is programmed appropriately at the FACP where the inputs are not mapped to the same zone as its
outputs.
For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document #15384.
Refer to the SLC Wiring Manual for more information.
40
NO NC C
NO NC C
AC
Trouble
Trouble
Controlling NACs, Aux Power, and Door Holders with NAC Sync
24VDC Aux Power
CDRM-300
FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
FACP
NAC or Remote
Sync Output
SLC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite fl-ps6cFire-lite fl-ps10Fire-lite fl-ps10c

Table of Contents