6-4 Quad SIO circuit pack (NT6M60xx)
Procedure 6-1
Replacing QSIO circuit pack (NT6M60AA or NT6M60BA) - slot 6
Step
Description
27
To clear any alarms on the standby processor, enter the following at the maintenance
terminal:
>RSERR STDBY 00 (cr)
Alarms will clear on the standby processor if there are no faults.
28
To place the active processor unit in PRIME mode, perform the following steps at the
Switch and Status Panel of the DPP:
a. Press the A/B Select Switch to match the active processor.
b. Press the O/P Mode Select Switch to P.
c. Turn the Mode Switch to the right and release.
29
To clear all alarms on the active processor, enter the following at the maintenance
terminal:
>RSERR ACT 00(cr)
Alarms will clear if there are no faults.
30
Enter the following command at the maintenance terminal to Switch Processors to
make the standby active:
>SWACT (cr)
The old standby is now the active processor.
WARNING
This should not be done at a high traffic period, it may cause a loss of AMA.
297-1001-539 Standard 01.03 September 2000