Omron C120 System Manual page 30

Optical remote i/o
Table of Contents

Advertisement

C500 Systems
Example 4 I/O Link Units
C500 CPU
Rack
C500 Master
3G2A5-RM001-(P)EV1
Example 5 I/O Link Units, Slaves, and Optical I/O Units
C500 CPU
Rack
C500 Master
3G2A5-RM001-(P)EV1
16
A maximum of 512 I/O points on I/O Units can be connected per Master, i.e.,
when the I/O Link Units are all set for 16 points each, up to 32 Units can be con-
nected to one Master on a C500. This would mean, however, that all I/O points
provided by the PC would be occupied and that no other I/O Units could be con-
nected. (The C20 I/O Link Unit has no setting for the number of I/O points and is
thus limited to 32 points.)
Optical Fiber Cable
(APF/PCF)
C500 CPU Rack
I/O Link Unit
3G2A5-LK010-(P)E
Up to two Slaves can be connected to one Master. Each I/O Link Unit requires 16
or 32 points (depending on the setting) and each Optical I/O Unit requires eight
points. These may be used in any combination of I/O which does not exceed the
total number of I/O points provided by the PC to which the Master is connected.
If more than 32 Units are connected to the same Master, a Repeater Unit must
be installed after the first 32 Units. The Slave's I/O Units are not counted in the 32
Units, but the I/O points must be included in the total number of I/O points.
Optical Fiber Cable (APF/PCF)
C500 CPU Rack
I/O Link Unit
3G2A5-LK010-(P)E
(Not including the I/O Units on the Slave Rack.)
C500 CPU Rack
Expansion
I/O Rack
I/O Link Unit
3G2A5-LK010-(P)E
Slave Rack
C500 Slave
3G2A5-RT002-(P)EV1
32 Units
Section
C20,
K-type
or P-type
PC
C20 I/O Link Unit
3G2C7-LK011-(P)E
Optical I/O Units
Repeater Unit
3G5A2-RPT01-(P)E
32 Units max.
2-5