Humidifier - Carrier 50CJ Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

9 - MAINTENANCE
■ Cleaning procedure

9.4 - Humidifier

■ Maintenance
Clean the humidifier once a year and replace its tank.
■ Cleaning or replacing the steam cylinder
This operation is necessary when the deposits that form on the active surface of the electrodes prevent the correct flow of current 
(alarms E08, E06).
To remove the tank:
- Drain the cylinder completely via the manual drain programme actuated by the control (See extract from the control manual:
paragraph 6.2, parameter no.911)
- Cut the power to the unit by turning it off at the switch or removing the fuses on the line,
- Remove the tank steam hose,
- Disconnect the main electrodes and remove the pins from the level electrodes,
- Remove the retention spring from the cylinder and lift the tank up and out.
In general, the steam tank can be reused after being descaled (scale on the electrodes prevents the free flow of water and current).
If the electrodes are too damaged to allow regeneration, the cylinder must be replaced: only the cylinder body and the gasket require 
replacement.
Check the gasket and replace it if need be. Put the tank back in place by following the above steps in reverse order.
■ Cleaning the unit and seasonal servicing
The unit must be checked and cleaned once a year or after it is shut off for an extended period. Remember to always first drain the 
water from the tank and to cut the power supply.
22
To access the electric elements, remove the removable side panel by
turning the latch a quarter turn
Accessing heating elements located behind the hydraulic coil.
Cleaning using an air nozzle.
To remove the heating elements:
- Unscrew the bolt and remove the washer, and push the pin 
backwards to release it from its housing. 
- Carry out this procedure in reverse when refitting.

Advertisement

Table of Contents
loading

Table of Contents