4.6

"Calibration" page

Parallax may occur on the touch screen depending on the mounting position and
perspective. To prevent any resulting operating errors, you may need to calibrate the touch
screen.
Requirement
● 1 Touch pen
● The "Calibration" dialog is open.
Procedure
1. Select "Start Calibration". The following dialog appears:
2. Briefly touch the center of the calibration crosshairs.
The calibration crosshairs are then displayed at three more positions. Briefly touch the
middle of the calibration crosshairs for each position.
Once you have touched the calibration crosshairs for all positions, the "Calibration
successful" message appears. The touch screen is calibrated.
Mobile Client900WXN
Operating Instructions, 04/2015, A5E35883103-AB
Parameter assignment of a Mobile Client
4.6 "Calibration" page
51