Siemens IM 155-6 PN ST Equipment Manual page 36

Simatic et 200sp interface module
Hide thumbs Also See for IM 155-6 PN ST:
Table of Contents

Advertisement

Interrupts, diagnostics, error, and system messages
5.3 Alarms
Coding of the extended channel diagnostics (as of firmware version V3.3.0)
With the IM 155-6 PN ST interface module, the following extended channel diagnostics are
reported:
Slot number
ChannelError-
Type (CET)
Module slot
0x0602
Slot 0
0x0602
0x0602
0x0602
0x0602
Server module slot 0x0610
Structure of the manufacturer-specific diagnostics data records (firmware version < V3.3.0)
The structure of the diagnostics data records is differentiated by the BlockVersion. The
following BlockVersion applies to the IM 155-6 PN ST interface modules:
Table 5- 8
IM 155-6 PN ST interface module
6ES7155-6AU00-0BN0
Manufacturer-specific diagnostics in the User Structure Identifier (USI)
The following manufacturer-specific diagnostics are signaled in the USI with the
IM 155-6 PN ST interface module:
Table 5- 9
USI no. W#16#...
0003
0004
0005
0006
0007
* As of IM 155-6 PN ST V1.1.x and GSD file 04/2013, this diagnostics is only signaled if the "Group
diagnostics: Missing supply voltage L+" parameter has been activated.
34
ExtendedChannel-
ErrorType (ECET)
0x0691
0x0693
0x0698
0x0699
0x069C
0x06B0
Structure of the manufacturer-specific diagnostics data records
Manufacturer-specific diagnostics in the USI
Diagnostics
Group diagnostics: Missing supply voltage L+ for the potential groups *
Diagnostics with missing server module
Diagnostics when more than one I/O module has been pulled
Diagnostics with incorrect BaseUnit
Diagnostics with incorrect bus configuration
Associated
Diagnostics
value AddValue
Slot
Station stop - module parameter "Poten-
tial group" faulty or incorrect BaseUnit in
actual slot (AddValue)
0x00
Diagnostics with missing server module
0x00
Diagnostics backplane bus too long
Slot
Diagnostics with incorrect bus configura-
tion
0x00
Diagnostics with incorrectly plugged
BusAdapter
0x00
Group diagnostics: Missing supply voltage
L+ for the potential groups
Note: The slot in which the light-colored
BaseUnit of the respective load module is
located is coded in the "ChannelNumber"
element.
BlockVersion
W#16#0101
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Equipment Manual, 10/2020, A5E03576904-AE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7155-6au01-0bn06es7155-6aa01-0bn0