Advertisement

Interrupts, diagnostics, error, and system messages
5.1 Status and error displays
PWR LED on the interface module
Table 5- 2
PWR status display on the interface module
PWR LED
Supply voltage not present or too small
Off
Supply voltage present
On
LK1/LK2 LED on the BusAdapter
Table 5- 3
LK1/LK2status display on the BusAdapter
LEDs LK1/LK2
There is no Ethernet connection between the
PROFINET IO interface of your PROFINET device and
Off
a communication partner (e.g. IO controller).
There is an Ethernet connection between the
PROFINET IO interface of your PROFINET device and
On
a communication partner (e.g. IO controller).
The "Node flash test" is run (the RN/ER/MT LEDs also
flash).
Flashes
LED display of configuration errors
Configuration errors of the ET 200SP distributed I/O system are output on the
interface
module by the ERROR (red) and MAINT (yellow) LEDs.
The following configuration errors are indicated by the LEDs:
• More than one I/O module pulled
• Missing server module
• Interruptions or short circuit on the backplane bus
Principle of operation
You determine the information for cause of the error with the LED error display. After
notification by the flash signal, the error type is displayed followed by the error location/error
code.
The LED error display
• is active during POWER ON as well as during operation.
• has priority before all other states displayed by the ERROR and MAINT LED.
• remains turned on until the cause of the error has been corrected.
28
Meaning
Meaning
Remedy
Check the supply voltage.
-
Remedy
Check whether the bus cable to the switch/IO con-
troller is interrupted.
-
-
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Equipment Manual, 10/2020, A5E03576904-AE