External Sampler setup
Parameter
Enable (2.11.4.1.)
Multiplier (2.11.4.2.)
Interval (2.11.4.3.)
Relay Duration (2.11.4.4.)
Assigned Relay (2.11.4.5.)
Relay Logic (2.11.4.6.)
A5E33329501
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Setting/
Description
Value
By selecting Enabled, the external sampler is
Enabled
now activated.
In this example, the LUT440 will activate the
external sampler every 1000 flow units (
1000
Units
defined above during initial application
setup).
In low flow conditions where the sampler may
not activate for extended periods of time, a relay
interval can be programmed to allow for sampler
24
activation after a defined number of hours. In
this example, activation should occur every 24
hours.
Duration of time in seconds that the relay will
0.2
energize or "tick".
Relay 2 has been selected for control in this
Relay 2
example as relay 1 has been allocated to the
Fail-safe alarm.
Default for control relay functions is Normally
Normally
Open. In this example, relay 2's coil will be Nor-
Open
mally Open, and will close for 0.2 seconds.
Flowrate
Page 61