Rated Conditions; Pneumatic Data - Siemens SIPART PS100 Compact Operating Instructions

Electropneumatic positioners
Table of Contents

Advertisement

Technical specifications

9.4 Pneumatic data

Digital output (DO), terminals 31 and 32
Maximum supply voltage U
"Conductive" state
"Locked" state
"Locked" is also the status if the device is faulty or analog input
(AI) is = 0 mA.
9.3

Rated conditions

Operating conditions
Ambient conditions for operation according to IEC 60068-2
Ambient temperature
Relative humidity
Pollution degree according to IEC 61010-1
Overvoltage category according to IEC 61010-1
Enclosure degree of protection
In accordance with IEC 60529
In accordance with NEMA 250
Corrosion protection according to EN ISO 9227:2012 and
EN ISO 12944:1999
6DR710 polycarbonate enclosure
6DR711 aluminum enclosure
Vibration resistance
Harmonic oscillations (sine) according to
IEC 60068-2-6
Bump (half-sine) according to
IEC 60068-2-27
Noise (controlled digitally) according to
IEC 60068-2-64
9.4
Pneumatic data
Pneumatic data
Pneumatic operating medium
Operating pressure
44
H
35 V
Permissible rated current 50 mA
Maximum terminal voltage 3 V
Overload-proof
I < 60 µA
For use indoors and outdoors.
-20 ... +80 °C (-4 ... +176 °F)
0 ... 100%
2
II
IP66
Type 4X
C5‑M medium durability
C5‑M medium durability
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
Compressed air, carbon dioxide (CO
gases
1.4 ... 7 bar (20.3 ... 101.5 psi)
Compact Operating Instructions, 05/2021, A5E50188940-AA
), nitrogen (N
), noble
2
2
SIPART PS100

Advertisement

Table of Contents
loading

Table of Contents