(2) Selection of circuit breaker and power cord.
Model
220~240V 50Hz
VEP027N432US
208~230V 60Hz
220~240V 50Hz
VEP034N432US
208~230V 60Hz
220~240V 50Hz
VEP042N432US
208~230V 60Hz
220~240V 50Hz
VEP042N432U
208~230V 60Hz
220~240V 50Hz
VEP048N432US
208~230V 60Hz
220~240V 50Hz
VEP048N432U
208~230V 60Hz
220~240V 50Hz
VEP060N432U
208~230V 60Hz
NOTES:
① Selection of circuit breaker and power cord in the above table is based upon unit's maximum
power (maximum current).
② Specification of power cord is based on the working condition where ambient temperature is
40°C and multi-core copper cable (working temperature is 90°C, e.g. power cable with YJV
cross-linked copper, insulated PE and PVC sheath) is lying on the surface of slot. If working
condition changes, please adjust the specification according to national standard.
③ Specification of circuit breaker is based on the working condition where ambient temperature
of circuit breaker is 40°C. If working condition changes, please adjust the specification
according to national standard.
Circuit breaker
Power supply
Number of ground
capacity
wire× Min sectional
(A)
area (mm
25
25
32
32
40
40
40
23
Number of power cord
× Min sectional area
)
2
1×2.5
1×2.5
1×2.5
1×2.5
1×6.0
1×6.0
1×6.0
(mm
)
2
2×2.5
2×2.5
2×2.5
2×2.5
2×6.0
2×6.0
2×6.0