proper dimension and remove burrs as well. See Fig.20.
(3) Y-type branch must be installed vertically or horizontally.
(4) Branch shall be isolated by insulating material that can bear 120° or even higher
temperature. The attached foam of branch cannot be taken as insulating material.
4.3.7 Thermal Insulation for Pipeline
(1) For multi VRF system, every copper pipe should be labeled so as to avoid misconnection.
(2) At the branch inlet, leave at least 500mm straight pipe section.
(3) Thermal insulation for pipeline.
1) To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid
pipe must be wrapped with thermal insulating material and adhesive tape for insulation
from the air.
2) Thermal insulating material shall be able bear the pipe temperature. For heat pump unit,
liquid pipe should bear 70°C or above and gas pipe should bear 120°C or above. For
cooling only unit, both liquid pipe and gas pipe should bear 70°C or above.
3) Example: Polyethylene foam (bear 120°C or above); foaming polyethylene (bear 100°C
or above).
4) Joints of indoor and outdoor unit should be wrapped with insulating material and leave
no gap between pipe and wall. See Fig.22.
5) Thermal insulating material of branches should be the same as that of the pipeline. The
attached foam of branches cannot be taken as insulating material.
6) When wrapping the tape, the later circle should cover half of the former one. Don't wrap
the rape too tight, otherwise the insulation effect will be weakened.