The recommended Maximum Temperature is below 54 degrees to
ensure maximum efficiency with condensing boilers.
If Maximum Temperature is set too low, there is a risk of not reaching
the desired temperature.
Configure settings of the Danfoss Link
Relay Output Configuration
NO (Normally Open) and NC (Normally Closed)
Cycle time
• 6 cycles/hour is recommended for condensing non-modulat-
ing gas boilers.
• 3 cycles/hour is recommended for condensing non-modulat-
ing oil boilers.
10
Danfoss Link™ DBR
VIIOS202
© Danfoss
Setpoint Limits
Configure the Minimum
Temperature and Maximum
temperature for Return Line
setpoint temperatures for
Danfoss Link™ DBR here.
(Note: You can only set these
setpoint limits within the
Dynamic mode.)