Error Code List - Mitsubishi Electric NZ2GN2S1-16D User Manual

Cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

11.7

Error Code List

The error codes are classified into the following three types.
Classification
Major error
Moderate error
Minor error
I/O module error codes are as follows.
Error code
Error type
0010H
Major error
0100H
Moderate error
0101H
Moderate error
0102H
Moderate error
0103H
Moderate error
0104H
Moderate error
0106H
Moderate error
0107H
Moderate error
0200H
Minor error
0201H
Minor error
0202H
Minor error
0203H
Minor error
0204H
Minor error
0205H
Minor error
Error name
Description and cause
Hardware error
Module hardware error
RWw/RWr setting error
When "Network Synchronous
Communication" in the network
configuration settings is set to
"Synchronous", System area
(RWw3/RWr3) is not set in "RWw/
RWr Setting".
Synchronization cycle
The synchronization cycle set in
setting error
the master station is not
supported by the I/O module.
Synchronous
Synchronous communication with
communication error 1
the master station has failed for a
certain period of time.
Synchronous
Synchronous communication with
communication error 2
the master station has failed for a
certain period of time.
External power supply
The external power supply voltage
OFF error
turns off.
IP address/station
The IP address/station number
number setting switch
setting switches are set outside
out of range error
the range of 1 to 120.
MODE switch incorrect
The MODE switch is set to an
incorrect state.
IP address/station
An IP address/station number
number setting switch
setting switch has been changed
changed error
with the module power supply on.
Function setting switch
The function setting switch 1 has
1 changed error
been changed with the module
power supply on.
Function setting switch
The function setting switch 2 has
2 changed error
been changed with the module
power supply on.
Function setting switch
The function setting switch 3 has
3 changed error
been changed with the module
power supply on.
Function setting switch
The function setting switch 4 has
4 changed error
been changed with the module
power supply on.
Function setting switch
The function setting switch 5 has
5 changed error
been changed with the module
power supply on.
Description
An error that cannot be recovered. The RUN LED turns off.
An error where the module cannot continue to operate. The ERR. LED turns on.
An error where the module can continue to operate. The ERR. LED flashes.
Action
Power off and on the module power supply.
If this error occurs again, the possible cause is a module
failure. Please consult your local Mitsubishi representative.
Correct the RWw/RWr setting of the network configuration
setting to assign the System area (RWw3/RWr3), and turn
off and on the module power supply or perform remote
reset.
Check the synchronization cycle of the master station, and
then turn off and on the power supply of the I/O module or
perform remote reset.
Take any of the following actions, and then turn off and on
the power supply of the I/O module or perform remote reset.
• For the synchronization cycle setting for the master
station, set a long cycle.
• Reduce the number of slave stations operating with the
CC-Link IE Field Network synchronous communication
function.
• Take measures against noise on the transmission path.
Take measures against noise on the transmission path, and
then turn off and on the module power supply of I/O module,
or perform remote reset.
• Check the state of the external power supply.
• Check if the power supply voltage satisfies the
specifications for the I/O module.
• Correct the timing of turning on or off External power
supply monitor request (RWw2.b9) if an error occurs
when starting or stopping the system.
Turn on the power supply with the IP address/station
number setting switches set to a value in the range 1 to 120.
Set the MODE switch correctly.
Return the IP address/station number setting switch to the
setting it had when the module was powered on.
Return the function setting switch 1 to the setting when the
module power supply was on.
Return the function setting switch 2 to the setting when the
module power supply was on.
Return the function setting switch 3 to the setting when the
module power supply was on.
Return the function setting switch 4 to the setting when the
module power supply was on.
Return the function setting switch 5 to the setting when the
module power supply was on.
11 TROUBLESHOOTING
211
11.7 Error Code List