Fixing The I/O Module (Waterproof Module) - Mitsubishi Electric NZ2GN2S1-16D User Manual

Cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

Fixing the I/O module (waterproof module)

When fixing the I/O module (waterproof module), tighten all of three screws.
If any of the screws is loose, the module will be greatly affected by vibration, causing failure of the module.
When installing the module, tighten screws within the following torque range.
Screw type
Module mounting screw/FG metal fitting screw (M4 screw)
• Do not put oil on the screws. Doing so may damage the screws.
• Tighten the screws with an applicable screwdriver. Tightening with an inapplicable screwdriver may damage
the screws.
Tightening torque range
0.83 to 1.11Nm
6 INSTALLATION AND WIRING
6
123
6.4 Installation

Advertisement

Table of Contents
loading

Table of Contents