Menu Options; Notifications - Lennox ComfortSense 8500 Installation And Setup Manual

Hide thumbs Also See for ComfortSense 8500:
Table of Contents

Advertisement

NAME
D24
HTG_TI
D25
HTG_PB
D26
SA_DF

Menu Options

During initial power up of the CS8500, the technician
settings menu will appear first. The S-bus address
option must be selected and a address set before
you can proceed. Use either the minus/plus buttons
or numeric keypad to enter the address. After the
s-bus address is set, press the back button to return
to the technician settings menu.
Table 6. Parameters
DESCRIPTION
Integration constant, heating
Proportional constant, heating
Supply air differential, determines if
suitable for heating
MIN
MAX
100
2550
10
255
2
30
2
30
0
20
Menu includes the following selections:

• Notifications

• Owner Settings
• Technician Settings
Notifications
When a system error occurs, a pop-up screen will
appear indicating the condition.
• Error code notification pop-up can be dismiss by
pressing the OK button. Contact the contractor to
resolve the issue.
Any active history for notifications are listed under
settings > notification.
1.
Press the down arrow icon next to the
notification to expand the notification for further
details.
2.
Press the contractor info option for assistance.
19
DEF.
UNIT
Notes
1200
SEC
0 is no
integration
120
Count
term.
4
°F
0 or 31 is no
PI control;
damper
operates
4
at reset
value.
10
°F