Lennox ComfortSense 8500 Installation And Setup Manual page 32

Hide thumbs Also See for ComfortSense 8500:
Table of Contents

Advertisement

Condition
Issue
Return Air
Temperature
Minor
Sensor (RT16)
problem
Advanced Airflow
Minor
Low Outdoor
Airflow
Advanced Airflow
Minor
Outdoor Airflow
Too High
OA Damper
Minor
Error (During
Free Cooling)
Not Economizing
Minor
When Outdoor
Air is Suitable
Economizing
When Outdoor
Minor
Air is Not
Suitable
Table 10. Error Codes
Display
System Action
Return
Displayed in
Air Temp
notification screen.
Sensor
Economizer
Displayed in
Fault
notification screen.
Economizer
Displayed in
Fault
notification screen.
Economizer
Displayed in
Fault
notification screen.
Economizer
Displayed in
Fault
notification screen.
Economizer
Displayed in
Fault
notification screen.
32
Action to Clear / Recovery
Condition
If measurement of the return
air temperature sensor is out of
specified range (including open /
short detection, the alarm will be
activated. Alarm will automatically
clear once in range condition is
detected.
Check sensor and wiring.
Outdoor airflow is too low so
the building is not getting the
designed outdoor airflow based
on IAQ.
Ventilation CFM is too high so the
RTU is wasting energy.
During free cooling damper is not
modulating.
May be due to the damper
motor being unplugged or
disconnected.
This may be due to damper
motor being blocked or stuck
open and therefore not closing.