NAME
D15
CLG_DF
D16
CLG_DF2
D17
CLG_DB
D18
CLG_TI
D19
CLG_PB
VOTING_
D20
HEAT
D21
HTG_DF
D22
HTG_DF2
D23
HTG_DB
Table 6. Parameters
DESCRIPTION
First cooling setpoint differential
2nd cooling setpoint differential
Cooling deadband
Integration constant, cooling
Proportional constant, cooling
(1st stage: 2nd) 0:0, 0:1, 1:1, 1:2
First heating setpoint differential
2nd heating setpoint differential
Heating deadband
MIN
MAX
0
3
0
12
0
3
0
12
1
4
4
16
100
2550
10
255
2
30
0
3
0:00
1:02
0
3
0
12
0
3
0
12
1
4
4
16
18
DEF.
UNIT
Notes
0.5
°F
2
Counts
1
°F
4
Counts
2
°F
8
Counts
1200
SEC
0 is no
integration
120
Count
term.
0 or 31 is no
PI control;
damper
4
°F
operates
at reset
value.
3
1:02
Votes
0.5
°F
2
Counts
1
°F
4
Counts
2
°F
8
Counts