Setup Guidance
The sensor input type, alarm type, control cycle, and other initial hardware settings that were made using DIP switches on previous models are
now made using the setup display on the E5ZN-SDL. Change the setup display by pressing the LEVEL and MODE Keys. The amount of time the
keys are pressed determines what parameter is entered.
Interpreting Typical Examples
Changing Parameters
M
M
M
Typical Example 1
0 K thermocouple −200 to 1300°C
Input type:
Control method: ON/OFF control
Alarm type:
2 upper limit
Alarm value 1: 20°C (Set the deviation in
Setup Procedure
Power ON
Set the unit number.
Set the channel number.
Initial Setting Level
Set input specifications.
Set the control method.
Set the alarm type.
Operation Level
Set alarm values.
Start operation.
Changing Values
This symbol means that
there are further
parameters. Keep pressing
the MODE Key until the
Set values in each
system switches to the
display can be
intended parameter.
changed by pressing
the U and D Keys.
Set point:
E5ZN unit number: 3
Channel number: 1
Power ON
Operation Level
Process value/
set point
Set the unit number and channel by
pressing the UNIT and CH Keys.
Press the
Control stops.
Initial Setting Level
Check the input
Input type
type.
M
For
ON/OFF
Select ON/OFF
control
control by using
the U and D
For PID
Keys.
control
M
Check the alarm
Alarm 1 type
type.
M
Press the
Operation Level
Press the U and
Process
D Keys to set the
value/set point
set point to 100°C.
M
Press the U
and D Keys to
Alarm value 1
set the alarm
value to 20°C.
M
To operate
Select "Run"
using the
U and D Keys.
To stop
M
Operation Level
100°C
Key for at least three seconds.
Key for at least one second.
4