Quick Start Guide
GFK-2948A

3. Configuration

You will need:
PACSystems RX3i CPU Firmware 7.18 or later.
Proficy Machine Edition version 8.50 SIM 9 or later.
GFK-2949, PACSystems RX3i Ethernet 104 Server Module User Manual, available
from the Emerson Global Support
Automation-Controls/support. You will need to refer to this manual to fully
configure and commission the EIS001.
3.1.

Configure EIS001 into Target CPU

Start the PME application, then open or create the project to contain the EIS001. After
configuring the rack, power supply, and CPU in the Project tab of the Navigator, select
a vacant slot in the main rack into which the EIS001 is to be installed. Right-click on
that slot icon and select Add Module. From the Communications tab of the Module
Catalog, select the IC695EIS001 module. This adds the EIS001 module from the drop-
down list into that location. Install the physical EIS001 module into the corresponding
location.