Checking Method for Key Components

2.8 Temperature Sensor

1) Outdoor temperature sensor : TH1
2) Discharge pipe(D-pipe) temperature sensor : TH2
1. Check the condition of installation and the contact of temperature sensor.
2. Check whether the connector contact of temperature sensor is normal.
3. Measure the resistance of temperature sensor.
3) Pipe temperature sensor : TH3
Resistance
1.07 kΩ±3.3 %(85 °C) 28 kΩ±7.7 %(85 °C)

2.9 Fan lock and Fan IPM Check

Checking Outdoor Fan Lock
1. Check alien substance in the Fan.
2. Check the imprisonment of fan
3. Check Motor Wire connection
(Motor
Motor PCB
Inverter PCB
4. Check the Motor. Refer to the below.
■ How to check the outdoor fan motor of BLDC
TH1
10 kΩ±1 %(25 °C)
200 kΩ±1 %(25 °C)
Please turn Fan, if fan is turn, ok.
Inverter or Main PCB)
Motor Wire Connection
Tester
Normal resistance (±10%)
TH2
5 kΩ±1 %(25 °C)
535 Ω±3.3 %(85 °C)
Motor PCB
45 Ω
45 Ω
45 Ω
- 98 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
TH3
Motor1
Motor2

Hide quick links: