2.1.2 Oil return control on heating mode
Outdoor Unit
Component
Inverter compressor
Fan
Main EEV
Subcooling EEV
4way valve 1
4way valve 2
Indoor Unit
Component
Fan
Thermo on unit EEV
Thermo off unit EEV
n Oil return operation time : 3 min for running step
n Starting condition:same as cooling mode
n Oil return process ends if compressor protection control starts
Starting
30 Hz
OFF
300 pulse
Min. pulse
ON
Heat Recovery : OFF
Heat pump : OFF
Starting
Normal control
Normal control
60~100 pulse
- 21 -
Running
Setting Value
Normal control
Max. pulse
Min. pulse
OFF
OFF
Running
Normal control
400~800 pulse
400~800 pulse
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Function
Ending
40 Hz
OFF
200 pulse
Min. pulse
ON
OFF
Ending
Normal control
1200
600
Normal Control
1200
600
60~100 pulse