Night Low Noise Function - LG MULTI V Service Manual

Hide thumbs Also See for MULTI V:
Table of Contents

Advertisement

Function

4.3 Night Low Noise Function

In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night
which has low cooling load.
Night low noise function setting method
RPM / Time Settings
Step
Judgment Time(Hr)
op1
8
op2
6.5
op3
5
op4
8
op5
6.5
op6
5
op7
8
op8
6.5
op9
5
op10
op11
Continuous operation
op12
op13
6.5
op14
6.5
op15
6.5
CAUTION
• Request installer to set the function during installation.
• In case the function is not used, set the dip S/W OFF and reset the power.
• If ODU Hz and RPM change, cooling capacity may go down.
Service PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button : "Func" Push
the '●' button
Select the Function using '▶', '◀' Button : "Fn3"
Push the '●' button
Select the Option using '▶', '◀' Button : "op1~op15"
Push the '●' button
Start the Night low noise function :
Save the selected option value in EEPROM
Operation Time(Hr)
9
10.5
12
9
10.5
12
9
10.5
12
10.5
10.5
10.5
- 30 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.