LG MULTI V Service Manual page 134

Hide thumbs Also See for MULTI V:
Table of Contents

Advertisement

Self-diagnosis function
Error No.
Error Type
Inv. PCB Heatsink
62
Temperature High
n Error diagnosis and countermeasure flow chart
Is Installation
Condition Normal?
Yes
Inv. PCB IPM Connection
Condition Normal?
Yes
Is ODU Fan Motor Normal?
Yes
Is Inv. PCB assembly
Normal?
Yes
Recheck Power and
Installation Condition
n Check Inv. PCB Screw Connection Condition
Error Point
Heatsink Temperature
is Over 100 °C
1. Check Pipe Clogging/ Distortion
2. Check Covering (Outdoor/Indoor Unit)
No
3. Check EEV Connector Assemble Condition/Normal Operation
4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Reassemble or Manage if abnormality Found
No
1. Check Inv. PCB Screw Connection Condition
Reassemble or Manage if abnormality Found
No
1. Check Outdoor Unit Fan Motor Operation or Lock
Reassemble or Manage if abnormality Found
No
1. Reset
Replace Inv. PCB Assembly
Check Screw Connection Condition
- 134 -
Main Reasons
1. Inv. PCB IPM Connection Condition Abnormal
2. Outdoor Unit Fan Motor Operation Abnormal
3. Outdoor Unit Inv. PCB Assembly Defect
4. Overload Operation (Pipe Clogging/ Covering/EEV
Defect/Ref. Overcharge)
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents