York CCWEB01 Operation Manual page 69

Vrf management system web enabled central controller
Table of Contents

Advertisement

No.
Event
1
The system does not
boot.
2
Applications start.
3
The actual state is not
4
Connection evaluation Verify that the Indoor units are
5
does not complete.
Items to be checked
Is the Hard Drive capacity
Is LAN properly wired and HUB
turned ON between the Unit and
Check if other Central controller
are connected.
Check that there is no error
between the computer and this
unit connection.
discrepancy between the adapter
The time indicated in the
application is the computer time.
Action
• Check if the Power of the required
equipments for the communication such as
HUB are turned ON.
• Check if the LAN is wired correctly.
• Check if this unit is in Self-check mode.
Refer to the Installation manual for the method
Clear the memory to create more than 1GB
increase memory with a hard drive with more
memory space.
Turn this Unit ON.
Ensure that LAN is properly wired and
HUB turned ON between the unit and the
computer.
To update the screen each time the
application may not switch.
screen.
System connection evaluation time may last up
to 20 minutes after startup.
System evaluation time can be reduced by
Remove the other Central controller and
Check if the LAN cable is wired correctly and if
the HUB and this unit power is turned ON.