Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
Table 5-6 Others Submenu Parameters Setup Ranges with Lower Limit, Default, and Upper Limit Settings
PARAMETER
NAME
PowerOnDelay
PVStartupVolt
PVSlowStartPwDelta
ErrSoftStartP
NormSoftStopP
NormSoftStartP
NormDeratingStep
StartUpMinTemp
HVRTTripVolt
LVRTTripVolt
LVRTPstReactiveI
LVRTNegReactiveI
PSet_Percent
QSet_Percent
ISOProtection
GFCIStaticValue
DOCR-071030-A (11/17/2020)
DESCRIPTION
Startup delay time
PV start-up voltage
The output power should be slow
increased due to the change of PV
illumination at the Rule21 standard.
Power startup step after Grid Fault
Normal power step in soft stop
Normal power step in soft startup
Normal Power Derating step
The minimum startup temperature
The trigger Voltage of HVRT
The trigger Voltage of LVRT
The coefficient of positive sequence
reactive current
The coefficient of negative sequence
reactive current
Local electric dispatch Active Power
setting value
Local electric dispatch Reactive Power
setting value
Minimum insulation resistance
The static threshold value of Leakage
current
SETUP RANGE
SETUP RANGE
(LOWER LIMIT,
(LOWER LIMIT,
DEFAULT & UPPER
DEFAULT & UPPER
LIMIT) IEEE1547-
LIMIT) RULE21
2018
(1,5,1200)
(1,5,1200)
(200, 330 ,400)
(200, 330 ,400)
{0.01%,10%,10%}
{0.01%,10%,10%}
{0.01%,0.16%,100%} {0.01%,2%,100%}
{0.01%,6%,
{0.01%,10%,100%}
100%}
{0.01%,4%,100%}
{0.01%,100%,100%}
{0.01%,6%,
{0.01%,100%,100%}
100%}
{-35,-30,-20}
{-35,-30,-20}
{100%,110%,135%}
{100%,110%,135%}
{70%,88%,100%}
{70%,88%,100%}
{0%,150%,300%}
{0%,150%,300%}
{0%,200%,300%}
{0%,20%,300%}
{0%,100%,100%}
{0%,100%,100%}
{-60%,0%,60%}
{-60%,0%,60%}
{1k,250k,2000k}
{1k,250k,2000k}
{100, 250 ,1000}
{100, 250 ,1000}
Page 68 of 101