Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
Table 5-2 Active Power Derating Setup Ranges with Lower Limit, Default, and Upper Limit for IEEE 1547-2018 and CA Rule 21
PARAMETER
NAME
OvrFrqMin
OvrFrqMax
OvrFrqSlop
RecoveryFrq
OvrFrqRecoveryT
VirtualDamping
OperationOverVol Operating overvoltage protection value {100%,120%,135%}
VwCurveV1
VwCurveP1
VwCurveV2
VwCurveP2
OpenLoopRespT
5.2.2.2.3
ReactivePowerDerating
The "ReactivePowerDerating" submenu is used to set the Grid reactive power derating parameters including PF
parameters and Q parameters, etc. The parameters are shown in Figure 5-10.
Note: The PF and Q value can be adjusted by remote software if the "Remote" is selected.
DOCR-071030-A (11/17/2020)
DESCRIPTION
The trigger frequency of
OverFrequency derating
The end frequency or Rate of
Overfrequency derating (Depends on
the specific standard)
The Rate of Overfrequency derating.
The recovery frequency of
OverFrequency derating
The recovery time of OverFrequency
derating
Resonance damping coefficient
Grid overvoltage derating starting
voltage V1
Grid overvoltage derating starting
power P1
Grid overvoltage derating end voltage
V2
Grid overvoltage derating end power
P2
Open loop response time
SETUP RANGE
SETUP RANGE
(LOWER LIMIT,
(LOWER LIMIT,
DEFAULT & UPPER
DEFAULT & UPPER
LIMIT) IEEE1547-
LIMIT) RULE21
2018
{60, 60.04,72}
{60, 60.04 ,72}
{60,62.532,72}
{60, 62.034 ,72}
{0.01%,30%,100%}
{0.01%,30%,100%}
{58.8, 59.964 ,66}
{58.8, 59.964 ,66}
{0,60,1200}
{0,60,1200}
{0,0,5}
{0,0,5}
{100%,120%,135%}
{100%, 106%,110%} {100%, 106%,110%}
{0%,100%,100%}
{0%,100%,100%}
{100%,110%,135%}
{100%,110%,135%}
{0%, 0%,100%}
{0%, 0%,100%}
{0.5,10,90}
{0.5,10,90}