Economizer Set-Up; Drain Pan Condensate Overflow; Switch (Optional); Low Ambient Operation - Trane Foundation EBC180 Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners cooling only and electric heat
Table of Contents

Advertisement

S S t t a a r r t t U U p p
Table 12. Enthalpy operation with DCV (CO
OA Good to
DCV
economize?
No
Below set
Yes
No
Above set
Yes
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
(b)
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Economizer Set-Up

Adjusting the minimum position (MIN POS/VENTMAX
on the SETPOINTS menu) sets the required amount of
ventilation air.
Table 13. Single enthalpy and dual enthalpy boundaries (parameters ES1 through ES5)
Temp. dry-Bulb
Enth.
(ºF)
Curve
ES1
80.0
ES2
75.0
ES3
70.0
ES4
65.0
ES5
60.0
HL
86.0
Note: For differential enthalpy there is a high limit boundary. The high limit boundary is ES1 when there are no stages of mechanical cooling
energized and HL when a compressor stage is energized.
N N o o t t e e : : To disable the economizer to do functional
testing, use a 10 mm wrench to completely
unsecure the shaft coupling. After testing,
tighten shaft coupling securely onto damper
shaft using minimum 120 lb-in. (13.6 Nm) to
maximum 180 lb-in. (20.3 Nm) torque.
Drain Pan Condensate Overflow Switch

(Optional)

The Condensate Overflow Switch (COF) is utilized to
prevent water overflow from the drain pan. The float
switch is installed on the corner lip of the drain pan.
When the condensate level reaches the trip point, the
COF relay energizes and opens the 24 Vac control
circuit which disables the unit. Once the 24 Vac control
32
sensor) - 2 speed fan
2
Y1-I
Y2-I
FAN SPD
Off
Off
Low
On
Off
Low
High
On
On
Off
Off
Low
On
Off
Low
High
On
On
Off
Off
Low
On
Off
Low
High
On
On
Off
Off
Low
On
Off
Low
High
On
On
Temp.
Enthalpy (btu/
dewpoint (ºF)
lb/ da)
60.0
28.0
57.0
26.0
54.0
24.0
51.0
22.0
48.0
20.0
66.0
32.4
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
24-v/On
0-v/Off
(a)
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
DELAY 24-v/On
(b)
0-v/Off
(a)
Ambient temperature controls the economizing cycle
by sensing the outside air dry bulb temperature.
13, p. 32
lists the five selectable dry bulb values (ENTH
CURVE) on the SETPOINTS menu.
Point P1
Temp. ºF Humid.% RH Temp. ºF
80.0
36.8
75.0
39.6
70.0
42.3
65.0
44.8
60.0
46.9
86.0
38.9
circuit is opened, a delay timer will prevent unit start-
up for three minutes.
Low Ambient Operation (Optional)
During low ambient operation, outside air temperature
below 50°F, the Low Ambient Controller will cycle the
outdoor fan motor "Off" and "On" based on discharge
pressure. The indoor fan motor (IDM) will continue to
operate and the outdoor fan will return to normal
operation once the ambient temperature is above 50°F.

10 Horsepower Motor Overload

10HP indoor fan motors are not internally protected.
For proper protection, ensure the adjustable dial on the
front of the overload (located in the control box) is set
to the nameplate FLA value of the indoor motor.
Occupied
VENTMIN L
VENTMIN L
VENTMIN H
VENTMIN L
VENTMIN L to Full-Open
Closed to Full-Open
VENTMIN H to Full-Open
Closed to Full-Open
VENTMIN L to VENTMAX
VENTMIN L to VENTMAX
VENTMIN H to VENTMAX
VENTMIN L to VENTMAX
VENTMIN L to Full-Open
Closed to Full-Open
VENTMIN H to Full-Open
Closed to Full-Open
Point P2
Humid.% RH
66.3
80.1
63.3
80.0
59.7
81.4
55.7
84.2
51.3
88.5
72.4
80.3
Unoccupied
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Table
RT-SVX50J-EN