Trane Foundation EBC180 Installation, Operation And Maintenance Manual page 30

Packaged rooftop air conditioners cooling only and electric heat
Table of Contents

Advertisement

S S t t a a r r t t U U p p
Table 8. Enthalpy operation with DCV (CO
OA Good to
DCV
economize?
No
Below set
Yes
No
Above set
Yes
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
Table 9. Dry bulb operation no DCV (CO
OA Good to
DCV
Y1-I
economize?
Off
None
No
On
On
Off
On
None
Yes
On
(a)
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
(b)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
30
sensor) - 1 speed fan
2
Y1-I
Y2-I
FAN SPD
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
sensor) - 2 speed fan
2
Y2-I
FAN SPD
Off
Low
Off
Low
High
On
Off
Low
Off
Low
High
DELAY 24-v/On
On
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
24-v/On
0-v/Off
(a)
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
DELAY 24-v/On
0-v/Off
(a)
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
(a)
0-v/Off
(b)
Occupied
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to Full-Open
Closed to Full-Open
VENTMIN to Full-Open
Closed to Full-Open
VENTMIN to VENTMAX
VENTMIN L to VENTMAX
VENTMIN H to VENTMAX
VENTMIN L to VENTMAX
VENTMIN to Full-Open
Closed to Full-Open
VENTMIN to Full-Open
Closed to Full-Open
Occupied
MIN POS L
MIN POS L
MIN POS H
MIN POS L
MIN POS L to Full-Open
Closed to Full-Open
MIN POS H to Full-Open
Closed to Full-Open
Unoccupied
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Unoccupied
Closed
Closed
Closed
Closed
RT-SVX50J-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Foundation ebc210Foundation ebc240Foundation ebc300

Table of Contents