Fuel Pipe Sizing - Briggs & Stratton Generator Owner's Manual

Briggs & stratton standby generator installation, start-up and owner's manual
Hide thumbs Also See for Generator:
Table of Contents

Advertisement

Available languages

Available languages

Fuel Pipe Sizing

Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.
Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour
NPT
10ft
15ft
1/2"
168
146
3/4"
346
293
1"
653
549
Natural Gas (sg=0.65)
Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour
NPT
10ft
15ft
1/2"
110
96
3/4"
277
192
1"
428
360
Liquid Propane (LP) (sg=1.50)
Briggs & Stratton Power Products Home Standby Generator
Installation, Start-Up and Owner's Manual
20ft
30ft
40ft
115
93
79
240
192
163
446
360
307
20ft
30ft
40ft
76
61
52
158
126
107
293
236
202
Listed values compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, please refer
to federal and local codes.
50ft
60ft
70ft
70
63
145
132
274
250
50ft
60ft
70ft
46
42
95
87
180
164
14
80ft
90ft
59
55
51
120
113
106
230
211
197
80ft
90ft
38
36
33
79
74
69
151
139
129
100ft
48
99
187
100ft
32
65
123

Hide quick links: