This rating is applicable to installations served by a reliable
normal utility source. This rating is only applicable to
variable loads with an average load factor of 80% of the
standby rating. The standby rating is only applicable for
optional standby power where the generator set serves as
the backup to the normal utility source.
Use the "Wattage Reference Guide" provided and mark those
circuits you consider "critical" or "essential". Make sure you
and your installer consider the generator's altitude above sea
level and the ambient temperature range when determining
total generator load.

Disconnect Box Mounting Guidelines

The disconnect box is a NEMA Type 3R enclosure suitable for
outdoor use. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Guidelines for mounting the disconnect box include:
• The disconnect box must be installed with appropriate
hardware for conduit connections.
• Install disconnect box on a firm, sturdy supporting
structure, making sure it is level and plumb.
• NEVER install disconnect box where any corrosive
substance might drip onto enclosure.
• Protect disconnect box at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive
vapors.
The typical installation of the disconnect box is depicted in
Figure 3. Discuss layout suggestions/changes with owner
before beginning installation process.
Figure 3 — Typical Disconnect Box Mounting
INSTALLATION

Fuel Inlet Dimensions

Figure 4, below, depicts the location of the fuel piping
connector.
Figure 4 — Generator Fuel Attachment Location
Fuel Piping
Connector

Removable Roof and Access Door

The Home Standby Generator is equipped with an enclosure
that has a removable roof and an access door for the control
panel.

To Remove Roof:

Remove the four screws and lift off.

To Remove Access Door:

1.
Remove roof as described above.
2.
Remove screw at top of access door.
3.
Pull access door outward (away) from unit while pulling
door upward and out of base. Door will come free of
generator enclosure.

To Install Access Door and Roof:

1.
Guide bottom of access door into base.
2.
Push access door until it is flush with sides.
3.
Replace door screw.
4.
Replace roof and screws.