Trane UHMB060ACV3VA Series Service Facts page 27

Upflow/ horizontal left and downflow/horizontal right, gas-fired, direct/non-direct vent, variable speed, modulating, condensing, communicating furnaces
Hide thumbs Also See for UHMB060ACV3VA Series:
Table of Contents

Advertisement

*UHMD120ACV5VA^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Unit
Airflow
Outdoor
Setting
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
3.5
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
4
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
5
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
2. ** Factory setting.
3. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
4. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton;
UHM-DHM-SF-1H
*UHM AIRFLOW - COOLING
External Static Pressure
0.1
0.3
CFM
1000
1024
Watts
122
168
CFM
1072
1094
Watts
140
188
1143
1164
CFM
Watts
160
211
CFM
1214
1233
182
236
Watts
CFM
1286
1303
Watts
207
264
1393
1408
CFM
Watts
250
311
CFM
1500
1513
300
365
Watts
CFM
1571
1582
337
406
Watts
1148
1169
CFM
Watts
161
213
CFM
1230
1248
Watts
187
242
CFM
1311
1328
217
274
Watts
CFM
1393
1408
Watts
250
311
1474
1488
CFM
Watts
287
352
CFM
1597
1607
352
421
Watts
CFM
1719
1727
Watts
427
503
1801
1807
CFM
Watts
483
563
CFM
1444
1458
273
336
Watts
CFM
1546
1557
Watts
324
391
CFM
1648
1657
Watts
381
454
1750
1757
CFM
Watts
447
525
CFM
1852
1857
522
604
Watts
CFM
2004
2006
Watts
651
742
2157
2156
CFM
Watts
803
902
CFM
2259
2255
966
966
Watts
HIGH 450 cfm/ton is for DRY CLIMATE setting.
Service Facts
0.5
0.7
0.9
1028
1022
1011
209
251
300
1097
1089
1076
234
281
331
1165
1157
1141
261
313
364
1234
1224
1207
291
347
400
1302
1291
1272
323
384
438
1405
1392
1370
377
444
500
1508
1492
1468
437
509
565
1576
1559
1533
481
555
611
1170
1161
1146
263
315
367
1248
1238
1221
297
355
408
1327
1315
1295
335
398
452
1405
1392
1370
377
444
500
1483
1468
1445
422
493
549
1601
1583
1556
497
572
628
1718
1699
1668
581
655
711
1797
1775
1743
642
712
768
1454
1440
1417
405
475
530
1552
1535
1510
465
538
594
1650
1631
1603
531
606
662
1748
1727
1696
603
676
732
1845
1823
1790
682
749
804
1992
1967
1947
811
863
966
2140
2050
1947
966
966
966
2140
2050
1947
966
966
966
NOTE:
CONTINUOUS
fan
mode during COOLING
operation may not be
appropriate in humid
climates. If the indoor
air exceeds 60% rela-
tive humidity or simply
feels
uncomfortably
humid,
it
is
recom-
mended that the fan
only be used in the
AUTO mode.
27