Trane UHMB060ACV3VA Series Service Facts page 26

Upflow/ horizontal left and downflow/horizontal right, gas-fired, direct/non-direct vent, variable speed, modulating, condensing, communicating furnaces
Hide thumbs Also See for UHMB060ACV3VA Series:
Table of Contents

Advertisement

Service Facts
*UHMC100ACV4VA^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Unit
Airflow
Outdoor
Setting
CFM
290 CFM/ton
Watts
CFM
310 CFM/ton
Watts
CFM
330 CFM/ton
Watts
CFM
350 CFM/ton
Watts
2.5
CFM
370 CFM/ton
Watts
CFM
400 CFM/ton
Watts
CFM
430 CFM/ton
Watts
CFM
450 CFM/ton
Watts
CFM
290 CFM/ton
Watts
CFM
310 CFM/ton
Watts
CFM
330 CFM/ton
Watts
CFM
350 CFM/ton
Watts
3
CFM
370 CFM/ton
Watts
CFM
400 CFM/ton
Watts
CFM
430 CFM/ton
Watts
CFM
450 CFM/ton
Watts
CFM
290 CFM/ton
Watts
CFM
310 CFM/ton
Watts
CFM
330 CFM/ton
Watts
CFM
350 CFM/ton
Watts
3.5
CFM
370 CFM/ton
Watts
CFM
400 CFM/ton
Watts
CFM
430 CFM/ton
Watts
CFM
450 CFM/ton
Watts
CFM
290 CFM/ton
Watts
CFM
310 CFM/ton
Watts
CFM
330 CFM/ton
Watts
CFM
350 CFM/ton
Watts
4
CFM
370 CFM/ton
Watts
CFM
400 CFM/ton
Watts
CFM
430 CFM/ton
Watts
CFM
450 CFM/ton
Watts
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton;
26
*UHM AIRFLOW - COOLING
External Static Pressure
0.1
0.3
0.5
714
734
739
79
118
157
765
784
789
88
128
168
816
834
838
96
138
179
868
884
887
103
149
192
919
934
936
117
161
205
995
1009
1009
135
181
227
1072
1084
1083
156
204
253
1123
1134
1132
171
220
271
862
879
882
105
148
190
924
939
941
118
162
207
985
999
1000
133
178
224
1046
1059
1059
149
196
244
1108
1119
1117
167
215
265
1200
1209
1206
197
248
301
1292
1299
1294
232
286
343
1353
1359
1353
258
314
373
1011
1024
1024
139
185
232
1082
1094
1093
159
207
256
1154
1164
1162
181
231
283
1225
1234
1230
206
258
312
1297
1304
1299
234
288
345
1404
1409
1402
281
340
400
1512
1514
1505
336
399
464
1583
1584
1574
377
444
512
1159
1169
1167
183
233
285
1241
1249
1245
212
264
319
1323
1329
1324
244
300
358
1404
1409
1402
281
340
400
1486
1489
1481
322
384
448
1609
1609
1599
393
461
530
1732
1730
1716
475
550
624
1813
1810
1795
536
617
694
HIGH 450 cfm/ton is for DRY CLIMATE setting.
0.7
0.9
733
722
194
231
782
770
206
244
831
819
220
258
880
867
234
273
929
916
249
290
1002
989
274
316
1075
1061
302
346
1124
1110
322
368
875
863
232
272
934
921
250
291
992
979
270
313
1051
1037
292
336
1109
1095
316
362
1197
1183
355
404
1285
1270
400
453
1344
1328
432
488
1017
1003
279
322
1085
1071
306
351
1153
1139
335
382
1222
1207
367
417
1290
1275
402
455
1393
1377
462
520
1495
1478
530
595
1564
1546
580
650
1158
1144
337
385
1236
1221
374
425
1315
1299
416
470
1393
1377
462
520
1471
1454
513
576
1588
1571
599
671
1705
1687
698
781
1783
1765
NOTE:
772
864
CONTINUOUS fan mode during COOL-
ING operation may not be appropriate in
humid climates.
ceeds 60% relative humidity or simply
feels uncomfortably humid, it is recom-
mended that the fan only be used in the
AUTO mode.
If the indoor air ex-
UHM-DHM-SF-1H