Periodic Servicing Requirements - Trane UHMB060ACV3VA Series Service Facts

Upflow/ horizontal left and downflow/horizontal right, gas-fired, direct/non-direct vent, variable speed, modulating, condensing, communicating furnaces
Hide thumbs Also See for UHMB060ACV3VA Series:
Table of Contents

Advertisement

Service Facts
PS-3 Inducer Learning Routine
Note:
Stage 1 = 40% (low) heat, Stage 2 = 100% (high) heat
When the furnace IFC receives a digital signal for
100% (high) heat from the comfort control it will
begin the PS-3 inducer learning routine.
The furnace will start the heating cycle in 65%
(medium) heat, if not already on, and then begins
the PS-3 inducer learning routine.
The furnace IFC will send a digital signal to the
variable speed inducer drive to run the inducer
motor at the preset factory 100% (high) heat
RPM.
The furnace IFC waits for PS-3 pressure switch to
close. A 24 Volt AC signal is sent to the furnace
IFC when the pressure switch closes.
If PS-3 does not close at the factory preset 100%
(high) heat RPM, the furnace IFC will continue to
signal the variable speed inducer drive to in-
crease the inducer speed in steps until PS-3
closes or until the maximum RPM for 100%
(high) heat is reached.
The furnace IFC enters a time delay so that the
heat exchanger and the recuperative cell warm
up to their high heat operating temperature. At
the end of this time delay, the inducer discharge
air temperature will be at its high heat operating
temperature and the density of the products of
combustion will be stabilized.
The furnace will now signal the variable speed
inducer drive to reduce the inducer speed in steps
until PS-3 opens.
When PS-3 opens, the furnace IFC will NOTE the
inducer motor RPM.
The furnace IFC then adds an additional number
of RPM to the 100% (high) heat inducer motor
NOTED RPM until PS-3 closes.
The furnace IFC now stores this learned inducer
operating RPM for 100% (high) heat in its
memory.
The furnace IFC will use this stored learned
inducer operating RPM for 100% (high) heat calls
it receives in the future.
If PS-3 is not closed when the inducer reaches its
maximum RPM, the furnace IFC will signal the
variable speed inducer drive to reduce the in-
ducer Motor speed in steps to its low heat
LEARNED SPEED.
The furnace IFC flashes its Red Fault LED three
times repeatedly. The furnace IFC will keep
operating at low heat for 10 minutes and then re-
try the PS-3 learning routine.
16
INDOOR BLOWER TIMING
Heating: The Integrated Furnace Control module
controls the Indoor Blower. The Blower
start is fixed at 45 seconds after ignition.
The FAN-OFF period is field selectable
via the User Interface menu at 60, 100,
140, or 180 seconds. The factory setting is
100 seconds.
Cooling:
Continuous Fan mode is 50% of the cool-
ing CFM. This is a selectable range on
the Comfort Control menu.
When in communicating mode, see Use Interface Menu
in furnace Installer's Guide.

PERIODIC SERVICING REQUIREMENTS

WARNING
!
Disconnect power to the unit before removing the
Blower door. Allow a minimum of 10 seconds for IFC
power supply to discharge to 0 volts.
Failure to follow this warning could result in property
damage, personal injury or death.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the service and/ or periodic mainte-
nance instructions for the Furnace and venting system,
could result in carbon monoxide poisoning or death.
1. GENERAL INSPECTION – Examine the furnace
installation annually for the following items:
a. All flue product carrying areas external to the
Furnace (i.e. chimney, vent connector) are clear
and free of obstruction. A vent screen in the end
of the Vent (flue) Pipe must be inspected for
blockage annually.
b. The vent connector is in place, slopes upward
and is physically sound without holes or exces-
sive corrosion.
c. The return air duct connection(s) is physically
sound, is sealed to the Furnace and terminates
outside the space containing the Furnace.
d. The physical support of the Furnace should be
sound without sagging, cracks, gaps, etc., around
the base so as to provide a seal between the sup-
port and the base.
e. There are no obvious signs of deterioration of the
Furnace.