Field Settings Table - Daikin EWAQ-ACV3 Installation Manual

Packaged air-cooled water chillers and packaged reversible air to water heatpumps
Table of Contents

Advertisement

Field settings table

First
Second
code
code
Setting name
0
User permission level
00
User permission level
1
Weather dependent set point
00
Low ambient temperature (Lo_A)
01
High ambient temperature (Hi_A)
02
Set point at low ambient temperature (Lo_TI)
03
Set point at high ambient temperature (Hi_TI)
2
Not available
3
Auto restart
00
Status
4
Not available
5
Not available
6
Not available
7
Not available
8
Not available
9
Cooling and heating set point ranges
00
Heating set point upper limit
01
Heating set point lower limit
02
Cooling set point upper limit
03
Cooling set point lower limit
04
Overshoot setting
A
Quiet mode
00
Quiet mode type
01
Parameter 01
C
Alarm output logic of EKRP1HB
00
Not applicable. Do not change the default value!
01
Output logic of the EKRP1HB remote alarm
input/output PCB
D
Benefit kWh rate power supply
00
Not available
01
Unit connection to benefit kWh rate power supply
02
Not applicable. Do not change the default value!
E
Unit information readout
00
Software version
01
EEPROM version
02
Unit model identification
03
Liquid refrigerant temperature
04
Inlet water temperature
Installation manual
21
Installer setting at variance with default value
Date
Value
Date
Default
Value
value
Range
3
2/3
–10
–20~5
15
10~20
40
25~55
25
25~55
0 (ON)
0/1
55
37~55
15
15~37
22
18~22
5
5~18
2
1~4
0
0/2
3
0
0
0/1
0 (OFF)
0/1/2
0
Read
only
Read
only
Read
only
Read
only
Read
only
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
Step
Unit
1
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
°C
°C