Specifications Of Standard Wiring Components - Daikin EWAQ-ACV3 Installation Manual

Packaged air-cooled water chillers and packaged reversible air to water heatpumps
Table of Contents

Advertisement

Precautions on wiring of power supply
For connection of the field wiring to the mainswitch, use the
instruction as described below.
2
For other connections, use a round crimp-style terminal for
connection to the power supply terminal board. In case it cannot
be used due to unavoidable reasons, be sure to observe the
following instruction (e.g. connection of the earth wire).
1
2
3
1
2 3
-
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
-
When connecting wires of the same gauge, connect them
according to the below figure.
Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
See the table below for tightening torques for the terminal
screws.
Tightening torque (N•m)
M4 (X1M)
M5 (X1M)
M5 (EARTH)
Attach an earth leakage circuit breaker and fuse to the power
supply line.
In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.
Specifications of standard wiring components
V3
W1
1~ 50 Hz
3N~ 50 Hz
230 V
400 V
L1
L2
L3
1
2
S12M
3
L1
L2
L3
X1M
X1M
(a)
Minimum circuit amps (MCA)
Recommended field fuse
(b)
Wire type
Size
Wire type of wiring between the units
(a) Stated values are maximum values.
(b) Only in protected pipes, use H07RN-F when protected pipes are not used.
Installation manual
13
1
3
Round pressure terminal
Cut out section
Cup washer
1.2~1.8
2.0~3.0
3.0~4.0
1
Earth leakage circuit
breaker
2
Fuse
3
Main switch
V3
W1
28.2
13.5
32 A
20 A
H05VV-U3G
H05VV-U5G
Wiring size must comply with the
applicable local and national code
H05VV-U4G2.5
The earth leakage circuit breaker must be a
NOTE
high-speed type breaker of 30 mA (<0.1 s).
For V3 model: Equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16 A and ≤75 A per phase.)
The wiring diagram can be found on the inside of the front plate of the
unit.
Connection of the thermostat cable
Connection of the thermostat cable depends on the application.
See also
"Typical application examples" on page
Thermostat requirements
Contact voltage: 230 V.
Procedure
1
Connect the thermostat cable to the appropriate terminals as
shown on the wiring diagram.
Heating/cooling thermostat
Terminal block
H C
N
1 2 4
H C
th
2
Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
When a room thermostat is connected to the unit,
NOTE
the heating and cooling schedule timers are never
available. Other schedule timers are not affected.
For more information on the schedule timers, refer
to the operation manual.
When a room thermostat is connected to the unit,
and the = button or o button is pressed, the
centralised control indicator e will flash to
indicate that the room thermostat has priority and
controls on/off operation and change over
operation.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
6.
Remote ON/OFF
Terminal block
H C
N
1 2 4
sw
reversible air to water heatpumps
4PW51587-1A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ewyq-acv3Ewaq-acw1Ewyq-acw1

Table of Contents