Cable connection (OLCT 60)
Remove power before wiring the OLCT 60 to the controller. The site must be
equipotential.
Connect the cable to the detector first and then connect the controller. Once the wiring is
completed, connect the shield of the cable to the ground terminal of the controller.
2.7.6
Cable connection (OLCT 60/DG10P remote)
Remove power before wiring the OLCT 60 to the controller. The site must be
equipotential.
First carry out the connection between the GD10P (rep. A) and the detector (rep. B) as shown in
Figure 20. The minimum distance is 3 meters minimum and the maximum is 30 meters (100 feet).
The type of cable to use is 01-IT-09-EG-FA or EG-SF or similar, see page 12.
Then connect the OLCT 60 as described previously.
14
Figure 19: wiring the OLCT 60 (d or id version)
3 meters minimum
30 meters maximum
+ 24 Vcc
0 V
Signal
NPO60GB
Revision F.2