Prepare Roof Penetrations; Multiple Vent/Air Terminations - Lochinvar Armor AWH0400N Installation & Operation Manual

Table of Contents

Advertisement

5
Vertical direct venting
Vent/air termination – vertical

Prepare roof penetrations

1.
Air pipe penetration:
a.
Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2.
Vent pipe penetration:
a.
Cut a hole for the vent pipe.
combustible or noncombustible construction, size
the vent pipe hole with at least a 1/2 inch clearance
around the vent pipe outer diameter:
• 5½ inch (140 mm) hole for 4 inch (102 mm) vent
pipe
• 7½ inch (191 mm) hole for 6 inch (152 mm) vent
pipe
b.
Insert a galvanized metal thimble in the vent pipe
hole.
3. Space the air and vent holes to provide the minimum
spacing shown in FIG. 5-1A.
4. Follow all local codes for isolation of vent pipe when
passing through floors, ceilings, and roofs.
5. Provide flashing and sealing boots sized for the vent
pipe and air pipe.

Multiple vent/air terminations

1. When terminating multiple Armor water heaters,
terminate each vent/air connection as described in this
manual (FIG. 5-2).
Terminate all vent pipes at the same height
WARNING
and all air pipes at the same height to avoid
possibility of severe personal injury, death,
or substantial property damage.
2. Place roof penetrations to obtain minimum clearance of
12 inches between edge of air intake elbow and adjacent
vent pipe of another water heater for U.S. installations
(see
FIG. 5-2). For Canadian installations, provide
clearances required by CSA B149.1 Installation Code.
3. The air inlet of an Armor water heater is part of a direct
vent connection. It is not classified as a forced air intake
with regard to spacing from adjacent water heater vents.
(continued)
Figure 5-2 Vertical Terminations with Multiple Water
Heaters
For either
VENT
AIR
Figure 5-3 Alternate Vertical Terminations with Multiple
Water Heaters
Installation & Operation Manual
12" MINIMUM VERTICALLY
FROM VENT OUTLET TO
ANY AIR INLET
VENT
AIR
12" MINIMUM FROM EDGE OF AIR
INTAKE PIPE TO ADJACENT VENT
PIPE FROM ANOTHER WATER HEATER
33