Rinnai RHEPM8020N Modulating Supplemental Manual page 23

High-efficiency (he+) series infrared gas heater

Advertisement

SPARK IGNITER SET UP
Use the following diagram to check the Igniter gap. If the gap is incorrect all adjustments should be made to the
GROUND PRONG/PIN ONLY! DO NOT BEND THE IGNITER PRONG!!!!
USE THE BLACK BARS BELOW AS A GUIDE FOR AD-
JUSTMENT.
USE THE BARS THAT COINCIDE WITH
THE FORMAT & SIZE OF THIS PUBLICATION .
IF
this manual is in
"booklet" format
8.5" x 11"
(pages folded in half)
then use these bars
OR
IF this manual is printed 8.5" x
11" "full page" format
use these bars
SERVICE CHECKS
Flame current passes through the flame from
the sensor to ground. The minimum flame cur-
rent necessary to keep the system from lock-
out is 0.7 microamps. To measure flame cur-
rent, connect an analog DC microammeter to
the FC- FC+ terminals per figure at right.
Meter should read 0.7 µA or higher. If the me-
ter reads below "0" on scale, meter leads are
reversed. Disconnect power and reconnect
meter leads for proper polarity.
3/16"
1/4"
1/4"
3/16"
Multipurpose Meter
23
AD-
Use Microamp
HE+ Series Modulating Supplemental Manual