Horizontal vent through the sidewall (Category III):
When installed with a horizontal vent through a sidewall, this heater is a Category III appliance,
◼
and venting materials must be approved for Category III applications.
All vent must be installed in accordance with local codes or, in the absence of local codes, with
◼
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
All vent must installed in accordance with these instructions, and the instructions of the vent
◼
manufacturer.
Do not mix vent components from different manufacturers in the vent system
◼
A single wall vent system may use a single continuous section of double wall vent pipe to pass
◼
through an exterior wall.
Any horizontal portion of the flue vent system must slope downwards away from the heater a
◼
minimum of 1/4" per foot run [63 mm/ 300 mm] toward the vent terminal.
All vent pipe from a single heater must be 4" [102 mm] diameter; common vent pipe for two
◼
heaters must increase to 6" [152 mm] at the point of connection of individual 4" vents
Use approved 4" [102 mm] (902000002) or 6" [152 mm] (902000007) horizontal wall vent ter-
◼
minal or an approved high-wind termination cap
Installation of the vent must prevent blockage by snow and protect building materials from deg-
◼
radation by flue gases.
Install termination cap a minimum of 18 inches (45 cm) from the outside wall to the inside edge
◼
of terminal opening to alleviate back pressure caused by turbulent wind conditions (See Fig.
8). This also ensures flue gases are directed away from the structure to protect building mate-
rials from degradation by the exhausted flue gases.
At most two 90° elbows can be installed in a horizontal vent
◼
A horizontal flue vent will not terminate less than 1 ft [30 cm] above grade level, unless its lo-
◼
cation is adjacent to public walkways, then it must not terminate less than 7 ft [2.1m] above the
walkway.
Clearance below a combustible overhang or soffit:
◼
• As indicated in FIGURE 8 for approved terminations: 4" [100 mm] 902000002 or 6" [150
mm] 90200000.
• For other approved terminations: Will terminate 3 ft [915 mm] or more below a combustible
soffit or overhang.
A horizontal vent termination must be a minimum of 6 feet [1830 mm] from an inside corner
◼
formed by two exterior walls.
A venting system shall be securely supported by noncombustible hangers suitable for the
◼
weight of the materials.
A slip joint in the horizontal section of a venting system shall be secured with quantity 3 x #8 x
◼
1/2" sheet metal screws to prevent sagging.
Seal single-wall vent seams and joints with Dow Corning 736 Heat Resistant Sealant 600°F
◼
[315°C] or equivalent, or follow the instructions of the vent manufacturer for sealing vent pipe
connections
USA specific requirements for horizontal vent are on the next page