 Install the devices of the system completely.
 Check the a-, b- and P-wire against each other for short-circuits.
 Switch on the mains voltage.
After switching on the voltage supply, the FBI610x starts automatically.

Note

The SIP Gateway restarts automatically after a voltage interruption, even if the
!
device was switched off.
Switching off the power supply during a storage process or software update can cause
!
a loss of data or a malfunction of the device.

Error detection and indication

Error at the TCS:BUS
Only operation mode PASSIVE: a-wire is not
connected / not supplied, a-b short-circuit or a-
and P-wire are interchanged / short-circuited
Only operation mode ACTIVE: a-b or a-P
short-circuited
Network error
defective network connection or no connection
to the SIP server
Network error
defective network connection or no connection
to the SIP server
*
No error during the start process, indication, lights up and expires after around. 40 sec if no error was detected.
Start browser: connection establishment PC – SIP Gateway

Prepare the intranet connection

The PC/Laptop must be equipped with a network connection and the device must be lo-
cated in the same subnet as the SIP-Gateway. If your network and server are working in
the 192.168.1 address area (C net), you can directly access the SIP-Gateway (provided
that another device does not use the IP address of the SIP-Gateway).
Otherwise the used PC/Laptop must be set temporary to an IP address within the address
area of the FBI610x to establish a connection with the SIP-Gateway. To install / modify
your network connection, please use the network installation assistant or the help menu of
your operating system (catchword: Install the network). If several FBI610x, which are in
delivery state, are to be installed within one network, the devices must be commissioned
one by one and assigned to a free IP address.
TCS TürControlSysteme AG, TCS Hotline Germany: hotline@tcsag.de
www.tcsag.de
8

Commissioning

ERR
error indication flashes
(1:7, 1 Hz)
ERR
error indication
flashes out
(7:1, 1 Hz)
4
error indication SIP
lights up *
Connect a-wire / check power
supply,
interchange a- and P-wire or re-
move short-circuit,
device is in standby mode again
Check the network, check data
transmission, check login data for
SIP server,
device is in standby mode again
Check the network, check the
data transmission, check the
SIP server,
device is in standby mode again