en | Adjustment of detection settings
2.
3.
4.
Automask
Notice!
All automasks stored in the volatile alarm memory of the camera are lost when the supply
voltage is interrupted or switched off. Automasks that already have been saved will remain
unaffected.
Notice!
If you change the settings of Verification time [s], it is necessary to renew the automasks.
1.
2.
3.
4.
P
Reset user interface
Notice!
All determined masks in the user interface will be deleted! Only automasks remain stored in
the alarm memory and can be regenerated.
If you want to reset the user interface to standard values:
1.
2.
P
2020.08 | 01 | F.01U.391.015
for each mask: 5 ... 120. A clock icon with a small smoke plume is displayed at the bottom
right-hand corner.
Verification time flames
The following settings (in seconds) are possible to assign an individual verification time
for each mask: 4 / 8 / 12 / 16. A clock icon with a small flame is displayed at the bottom
right-hand corner.
Change the size and shape of the rectangle to your specific needs.
Move the mask to the desired area in the picture.
Select Set to confirm the changes.
Navigate to Configuration > Alarm > Fire detection.
Select Automask
The system automatically generates predefined masks from the alarm memory. The
automasks are illustrated as rectangles with red dashed border.
Adjust the automask to your specific needs.
If it is necessary, you can add individual masks (Add mask).
Select Set to confirm the changes.
Automasks were added to the system.
Click on Defaults.
Press OK to confirm.
The system resets the user interface for fire detection to the standard settings.