STARTUP / TROUBLESHOOTING
In Figure 5-7, the 1 in Bit 10 indicates that slot seven in Base 0 contains a
malfunctioning or incorrectly configured module (I/O mismatch). All other slots
either contain a working module or no module at all.
1
Bit #
Value
0
8
Slot #
Base
Figure 5-7 Example of a Status Word With a Bit Set
When a distributed base loses communication with the PLC, the
appropriate bit in STW02 shows a 1, and the corresponding bits
in STW12 to STW18 show zeroes, even if modules on that base
have failed or been incorrectly configured. That is, modules do
not show failures on a base that is not present.