Location Of Power Supply In Base - Siemens SIMATIC TI525 Hardware And Installation Manual

Table of Contents

Advertisement

6. Use 14 AWG solid or stranded wire for connection to the power
source; use of smaller wire is not recommended. If stranded wire is
used, the wire should be twisted and tinned.
7. Insert the green ground wire into the connector labeled "ground."
8. Insert the black AC line and white AC neutral wires into the power
supply wire connectors labeled "AC line" and "AC neutral,"
respectively.
9. After inserting the wires, secure them by tightening the terminal
block screws.
10.
Enable power.
Bezel screws
The base power budget is determined from the power provided by the base
power supply and the requirements of the particular modules used. When
determining the I/O system layout, do not exceed the maximum power available
from the power supply. The total power requirement for all modules drawing
power from a Series 505 base must be less than or equal: 55 W at +5 VDC and
3.75 W at –5 VDC.
Hardware and Installation User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
INSTALLATION
WARNING
Connecting the power supply leads to the
wrong terminals creates a potential shock
hazard
that
could
equipment or injury to personnel. Be sure
that the polarity on all power supply leads is
correct.
Figure 3-19 Location of Power Supply in Base
3-26
cause
damage
to

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic ti535

Table of Contents