Connection Of External Cables; Line Lengths - Mitel MX-ONE Installation Instruction

Table of Contents

Advertisement

4
4.1
4.2
21/1531-ASP11301 Uen C 2017-03-28

CONNECTION OF EXTERNAL CABLES

GENERAL
Cabling to the MDF uses prefabricated cables.
Twisted, shielded, pair-cables are to be used for cabling between the PBX and MDF or
PBX and PBX (Media Gateway - Media Gateway).
The cable length from the exchange to the MDF shall not be shorter than 3 meters (118
inches).

LINE LENGTHS

ELU26
The following three connection alternatives are based on the usage of a 75 ohm
twisted pair cable, 120 nF/km and wire 0.6 mm or a 150 ohm twisted pair cable,
30 nF/km and wire 0.6 mm or 125 ohm/km DC.
1000 m, point-to-point with one terminal.
500 m, extended passive bus with 8 terminals.
100 m, short passive bus with 8 terminals.
ELU31
For information see Installation Instructions for CORDLESS PHONES.
ELU33
600 m if using a twisted pair cable with wire diameter 0.4 mm.
1000 m if using a twisted pair cable with wire diameter 0.5 mm, point-to-point with
one terminal.
ELU34
6000 m if using a twisted pair cable with wire diameter 0.4 mm.
9000 m if using a twisted pair cable with wire diameter 0.5 mm.
TLU76
260 m if using a 120 ohm twisted pair cable without repeater
TLU77
260 m if using a 120 ohm twisted pair cable without repeater
TLU79
see Figure 31: Connecting TLU79 to TLU79 through MDF (8 pairs) on page 39.
TLU80
7000 m if using a twisted pair cable with wire diameter 0.4 mm. 11000 m if using
a twisted pair cable with wire diameter 0.5 mm.
TLU83
5000 m if using a twisted pair cable with wire diameter 0.4 mm.
8000 m if using a twisted pair cable with wire diameter 0.5 mm.