TABLE 3 – ELECTRICAL DATA (CONTINUED)
ELECTRIC HEAT
NOMINAL VOLTAGE
KW
208/3/60
230/3/60
AMPS
AMPS
40
96
80
193
108
260
150
200
250
TABLE 4 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
Limitations
Design Airfl ow Limits
CFM* (min to max)
Entering Wet Bulb
Temp F° (min/max)
Entering Dry Bulb
Temp F° (min/max)
Ambient Temp F°
without Low Amb option
Ambient Temp F°
with Low Amb option
* Cooling Only Units
YORK INTERNATIONAL
460/3/60
575/3/60
AMPS
AMPS
96
48
40
193
96
80
260
130
109
181
151
241
201
301
251
50
55
60
10000 -
12000 -
14000 -
22500
24000
27000
57/75
57/75
57/75
68/90
68/90
68/90
45/120
45/120
45/120
0/120
0/120
0/120
Model Size
65
70
75
14000 -
14000 -
14000 -
27000
32000
32000
57/75
57/75
57/75
68/90
68/90
68/90
45/120
45/120
45/120
0/120
0/120
0/120
FORM 100.50-NOM1 (604)
80
85
90
14000 -
14000 -
18000 -
32000
32000
36000
57/75
57/75
57/75
68/90
68/90
68/90
45/120
45/120
45/120
0/120
0/120
0/120
2
95
18000 -
36000
57/75
68/90
45/120
0/120
23

Hide quick links: