Direct Connect With Outside Air; Direct Connect Without Outside Air - Quadra-Fire TREKKERI-MBK Installation Manual

Trekker insert pellet
Hide thumbs Also See for TREKKERI-MBK:
Table of Contents

Advertisement

C. Direct Connect with Outside Air
NOTE: In Canada, only a full reline is allowed per ULC S628-93, ORD ULC C1482-M1990.
Outside Air through Rear Wall
Figure 18.2
NOTE:
• Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to scale.
• Actual installation may vary due to individual
design preference.
Never draw outside combustion air from:
Wall, floor or ceiling cavity
Enclosed space such as an attic or garage
18
Note:
• Use metal plate around exhaust vent
pipe
and
seal
all
edges
non-flammable insulation such as
fiberglass, mineral wool or ceramic
material.
• DO NOT use high temperature cauling
materials to seal any edge to prevent
future serviceability
CAUTION
D. Direct Connect without Outside Air
with
Figure 18.2
Fire Risk.
Inspection of Chimney:
• Masonry
• Meets minimum standard of NFPA 211
• Factory-built chimney must be a minimum
NOTE: In Canada, where passage through a wall or
partition of combustible construction is desired, the
installation shall conform to CAN/CSA-B365.
7082-153K
Note:
• Use metal plate around exhaust vent
pipe
and
seal
non-flammable insulation such as
fiberglass, mineral wool or ceramic
material.
• DO NOT use high temperature cauling
materials to seal any edge to prevent
future serviceability
WARNING
chimney
good condition.
6 inch (152mm) UL103 HT.
all
edges
with
must
be
in
01/21