Patterson-Kelley SOLIS SL-1500 Installation & Owner's Manual page 37

Gas fired boiler with control system
Table of Contents

Advertisement

For correct installation of a
vent system, read all of these
instructions and refer to the
vent manufacturer's
instructions.
Failure to use a proper vent
system (types and materials)
as described in this manual
will void the appliance
warranty and may result in
rapid deterioration of the
venting system, creating a
health or life safety hazard.
Faulty vent installation can
allow toxic fumes to be
released into living areas.
This may cause property
damage, injury, or death
power to the damper motor, opening the damper.
limit switch completes the Air Damper Interlock circuit (120VAC) which allows the appliance to proceed
to ignition.
External power supplies are required for Relay A, Relay B, Relay
C and Relay D. Because power is provided from an external
source, the power is still present when the appliance is turned off.
Check all voltage sources have been disconnected prior to
servicing. Failure to do so could result in electrocution, injury, or
N
!
OTICE
Relay A, Relay B, Relay
C, and Relay D are
rated for a maximum
voltage of 240VAC and
a maximum current
capacity of 1/2 Amp.
Customer must supply
fusing for all current
connected to the relays.
Connecting a motorized
damper which exceeds
the voltage or current
capacity of the relay
could cause permanent
damage to the relay.
Revised: March 15, 2021
Released: March 15, 2021
NOTE: The power source to drive the damper actuator motor must
be provided externally. The appliance DOES NOT provide a
power source for this purpose.
NOTE: Combustion air dampers other than those listed in the table
above may require voltages other than 120VAC. This is
acceptable, provided the required voltage does not
240VAC.
NOTE:
The Air Damper Interlock circuit for the end limit switch is
always 120VAC which is sourced from the appliance itself. All end
limit switches must be rated for 120VAC.
Motorized combustion air dampers must be powered from an
external power supply other than the appliance. The figure below
shows a sample installation in which Relay C is user-selected to
operate a 120VAC motorized air damper. Relay C is normally-
open, so when the appliance is in standby, the combustion air
damper remains closed. Once a call for heat is received, Relay C
closes the 120VAC circuit (external power supply) which provides
Once the motorized damper is fully-open, its end
FUSED
© Patterson-Kelley 2021
All Rights Reserved.
P-K SOLIS™
Gas Fired Boiler
Technical Service 1.877.728.5351
exceed
®
Note: The NURO
control allows
the user to allocate Relay A, B, or
C for use with a motorized
combustion air damper. The
figure above shows Relay C in
use for the motorized combustion
air damper. Depending on the
user-configuration, Relay A, Relay
B, or Relay C can be selected to
operate the combustion air
damper.
2701000090 P-K SOLIS NURO Installation and
Owners Manual (Rev A).docx
Page 27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solis sl-2000Solis sl-2500Solis sl-3000Nuro

Table of Contents