2 ] Specification Of Ew-50 - Mitsubishi Electric MEHITS CH Technical Manual

Air conditioning control systems
Table of Contents

Advertisement

[3. Specification ]
[2] Specification of EW-50
Item
Number of units which can be connected and
controlled
Dimensions (W × H × D)
Weight
Power supply
Communication I/F
Equivalent power supply
Equivalent power consumption
Equivalent number of units
Temperature
Ambient
conditions
Humidity
Material
Power consumption
Installation conditions
*1: The number of indoor units which can be controlled may vary depending on the model of indoor units. The number of units which can be
controlled by the DIDO controller (PAC-YG66DCA) varies depending on the number of channels used (one channel for controlling one
unit).
*2: Up to 200 indoor units can be controlled by combining with AE-200.
50 indoor units per EW-50 (
172 × 209 × 92 mm (6-13/16 × 8-4/16 × 3-10/16 in)
** 172 × 253 × 92 mm (6-13/16 × 10 × 3-10/16 in) when using L-fittings
1.7 kg (4 lbs)
100–240 VAC ± 10%; 50/60 Hz Single-phase
M-NET
24 V DC (with power supply connector CN21, power supply from main unit)
LAN
100BASE-TX
1.5
0
0
Operating
temperature
-10°C – +55°C (+14°F – +131°F)
range
Storage
temperature
-20°C – +60°C (-4°F – +140°F)
range
30%–90% RH (Non-condensing)
Main unit: Electrogalvanized sheet steel
12 W
Only in a metal control box indoors